NEC 210.52(E) · Homes

Outdoor receptacles at homes, decks and balconies

One- and two-family homes need an outdoor receptacle at both the front and the back, reachable from grade and no more than 6½ ft above it. Balconies, decks and porches within 4 in. of the house need one too.

What the code requires

For a one-family home, and for each grade-level unit of a two-family home, at least one receptacle outlet is required at the front and at the back of the dwelling. Each must be readily accessible from grade and no more than 6½ ft above grade.

Balconies, decks and porches that are within 4 in., measured horizontally, of the dwelling unit need at least one receptacle outlet that can be reached from that surface. It may be no more than 6½ ft above the walking surface.

This page covers one- and two-family dwellings and balconies, decks and porches. The outdoor receptacle rule for multifamily buildings is not covered here.

On the job

  • A receptacle on a porch a few steps up can count as the front or back receptacle if it is readily accessible from grade.
  • A freestanding deck built within 4 in. of the house still needs its own receptacle. The 4-in. figure was chosen to match the building code.
  • Outdoor receptacles at homes need GFCI protection under 210.8(A)(3), and other outdoor outlets under 210.8(F). A temporary 210.8(F) exception for listed HVAC equipment, added by TIA 23-3, expired Sept 1, 2026. Confirm with your building department how this applies to your project.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond