CSLB #354550 · C-10 Electrical
CK Electric and Sons · Since 1978
ServicesEV chargersFree toolsCode libraryWorkService areasAboutContact

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond

NEC 210.8(F) · Homes

GFCI for outdoor outlets at homes, including A/C units

At dwellings, outdoor outlets on single-phase circuits of 150 V or less to ground and 50 A or less need GFCI protection. The exception for listed HVAC equipment expired September 1, 2026, so new and replacement outdoor A/C units are now covered.

What the code requires

For dwellings, all outdoor outlets, not just receptacles, need GFCI protection when supplied by single-phase branch circuits rated 150 V or less to ground and 50 A or less. Receptacles for snow-melting or pipe-heating equipment covered by 210.8(A) Exception 1 are excluded.

The rule specifically includes outlets in garages with floors at or below grade, accessory buildings and boathouses. If equipment supplied by a covered outlet is replaced, the outlet must be given GFCI protection at that time.

Lighting outlets are exempt, other than crawl-space lighting covered by 210.8(C). Listed HVAC equipment was also exempt, under an exception added by TIA 23-3, issued August 12, 2022, before the 2023 edition was printed. That exception expired September 1, 2026.

A proposed TIA (Log 1924) to extend the HVAC exception to September 1, 2028 failed on a 10–10 vote of the code-making panel. ACCA and AHRI have appealed to the NFPA Standards Council. As of October 8, 2026, the requirement applies while the appeals are pending. Confirm the current status with your building department.

On the job

  • Since September 1, 2026, a new outdoor A/C condenser or heat pump at a home needs a GFCI-protected circuit under the printed 2023 text.
  • Replacing a condenser or heat pump also triggers GFCI protection for the outlet that supplies it, even when the existing circuit is old, because the rule covers replaced equipment.
  • The HVAC industry has raised nuisance-tripping concerns with some equipment on GFCI protection, which is the subject of the pending appeals.
  • No California amendment to this rule was found among the 2025 California Electrical Code amendments reviewed for this page, so the printed September 1, 2026 sunset appears to apply as written. Check with your building department before relying on any later NFPA action.

Exceptions that matter

  • Lighting outlets, other than crawl-space lighting outlets covered by 210.8(C).
  • Listed HVAC equipment was exempt only until September 1, 2026. A proposed extension was rejected and is under appeal, so confirm the current status with your building department.

What changed in 2023

The 2023 edition added the garage, accessory building and boathouse list, added the rule that replacing equipment supplied by a covered outlet triggers GFCI protection for that outlet, dropped the 2020 delayed effective date for HVAC equipment with power conversion equipment, and added the temporary exception for listed HVAC equipment that expired September 1, 2026.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond