CSLB #354550 · C-10 Electrical
CK Electric and Sons · Since 1978
ServicesEV chargersFree toolsCode libraryWorkService areasAboutContact

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond

NEC 422.16 · Homes

Cords for dishwashers, disposals and range hoods

Disposals, dishwashers, trash compactors, range hoods and over-the-range microwaves may be plugged in if the manufacturer's instructions identify a suitable cord and the cord length, receptacle location and grounding meet set limits, such as a 3 to 6.5 ft cord for a dishwasher.

What the code requires

In-sink waste disposers: the cord must be 18 to 36 in. (450 to 900 mm) long, with an equipment grounding conductor and a grounding-type plug. The receptacle must be accessible and located to protect the cord.

Dishwashers: the cord must be 3 to 6.5 ft (0.9 to 2.0 m), measured from the face of the plug to the plane of the rear of the appliance. Trash compactors: 3 to 4 ft. The dishwasher receptacle goes in the space next to the dishwasher's space; a trash compactor's receptacle may be in the compactor's own space or next to it. Where the cord passes through an opening, it needs a bushing, grommet, smoothed edge or other approved protection.

Range hoods and over-the-range microwave/hood combinations: the cord must be 18 in. to 4 ft (450 mm to 1.2 m), with a grounding-type plug. The receptacle must be on an individual branch circuit, accessible and located to protect the cord. Wall ovens and counter-mounted cooktops may also be cord-connected if the cord is identified for that use and the plug suits the temperature of the space.

Cord-connected heated appliances with surfaces over 121 °C (250 °F) that the cord could touch need a heater-type cord from Table 400.4 (422.16(A)(3)).

On the job

  • A dishwasher receptacle placed behind the dishwasher is a common correction. It belongs in the adjacent cabinet space.
  • A cabinet hole with no grommet or bushing for the cord is a correction.
  • A range-hood receptacle that shares a circuit with other outlets is a correction. It needs an individual branch circuit.
  • Cords shorter or longer than the limits are a correction, so the appliance's cord length matters when planning the receptacle location.

Exceptions that matter

  • Listed appliances marked as protected by double insulation do not need a grounding-type plug.

What changed in 2023

In 2023, the rule requiring heater-type cords where a cord could touch hot appliance surfaces was relocated into this section as 422.16(A)(3), from 422.43(A), and the old limit to appliances rated over 50 watts was dropped.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond