NEC 404.2(C) · Homes and commercial

Neutral wire required at light switches

Where switches control lighting in bathrooms, hallways, stairways, habitable rooms or occupiable spaces, the code generally requires a neutral wire at the switch location so smart switches can work. The 2023 NEC removed the exemption for boxes that could take a new cable later.

What the code requires

A grounded (neutral) conductor must be provided at switch locations that control lighting in bathrooms, hallways, stairways, and habitable rooms or occupiable spaces, when that lighting is fed by a general-purpose branch circuit with a neutral. If several switch locations control the same lights and the whole floor area can be seen from them, only one of those locations needs the neutral.

Under the 2023 NEC, the neutral is not required in four cases: a raceway with room for a neutral enters the box; snap switches with integral enclosures are used under 300.15(E); the lighting is controlled by automatic means; or the switch controls a receptacle rather than lighting.

Where a switch needs line-to-neutral voltage to power its electronics in standby, the neutral must be connected to it, under 404.22.

On the job

  • Switch loops with no neutral in bedrooms, bathrooms and hallways are a common correction.
  • Smart switches that need a neutral must have one connected; installing them without it is a frequent problem.
  • The neutral is required at rough-in even if standard switches go in. Since 2023, an accessible box that could take a new cable later no longer excuses it.

Exceptions that matter

  • For replacement or retrofit switches in locations wired before your area adopted this rule, where a neutral cannot be extended without removing finish materials, electronic control switches without a neutral connection are allowed, limited to 5 per branch circuit and 25 per feeder.

What changed in 2023

The 2023 NEC deleted the exemption for a switch box that could be reached to add a cable later without removing finish materials.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond