NEC 705.13 · Homes and commercial

Energy management systems (formerly PCS) for solar

An energy management system, which many people still call a power control system or PCS, may limit the current that solar or battery sources put on busbars and conductors. Where one is used, its setting counts as the source current in busbar calculations.

What the code requires

In the 2023 NEC, 705.13 is titled Energy Management Systems (EMS). In 2020 the section covered Power Control Systems, and many people still use the PCS name. Revisions for the 2026 NEC return to the power control system name, but California's current code is based on the 2023 NEC.

The rule itself is short. An energy management system that meets 750.30 may limit the current and loading on busbars and conductors fed by one or more interconnected power production or storage sources. An informational note says a listed power control system is one type of EMS: it monitors multiple sources and controls current to keep busbars and conductors from overloading. The related product standards are UL 1741 and UL 916.

Under 705.28(A)(2), where an EMS controls the equipment, the EMS current setpoint is used as the source's maximum current, and that number then goes into the 705.12 busbar calculations and the 705.28 conductor calculations. A lower setting means a smaller number goes into that math.

On the job

  • The busbar and conductor calculations use the EMS current setting, so the setting in the equipment needs to match the number used in those calculations.
  • Under 750.6, new in the 2023 NEC, the energy management system must be listed.

What changed in 2023

The 2023 NEC replaced the 2020 power control system section and its detailed (A) through (E) rules with this short EMS rule, and Article 750 now requires an EMS to be listed.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond