NEC 300.4 · Homes and commercial

Protecting cables from nails and screws

Cables through holes in wood framing need the hole edge at least 1¼ in. from the edges of the wood, or a steel plate or bushing at least 1/16 in. thick covering the wiring.

What the code requires

Wiring through bored holes in wood framing must be placed so the edge of the hole is at least 1¼ in. from the edges of the wood member. If it cannot be, a steel plate or bushing at least 1/16 in. thick must cover the wiring. Where wiring sits in a notch in the wood, a steel plate at least 1/16 in. thick is required, installed before the wall or ceiling finish.

Wiring in a shallow groove needs a steel plate or sleeve at least 1/16 in. thick, or at least 1¼ in. of free space, for its full length.

Under metal-corrugated roof decking, the code requires at least 1½ in. between the lowest surface of the deck and the top of any cable, raceway or box. Wiring may not be concealed inside the decking.

Where raceways carry conductors of 4 AWG or larger into an enclosure, the conductors must be protected by a smoothly rounded insulating or listed metal fitting, secured insulating material, or a threaded hub. That protection goes in before the conductors are pulled, and an insulating bushing may not be used to secure the raceway.

On the job

  • Missing nail plates where holes are closer than 1¼ in. to the edge of a stud or joist are a common correction.
  • Cable or MC run tight against the underside of a metal roof deck is a frequent fail.

Exceptions that matter

  • Steel plates are not required for rigid metal conduit, intermediate metal conduit, PVC, RTRC or EMT.
  • Listed and marked plates thinner than 1/16 in. are allowed if they give equal protection.
  • The roof-deck spacing does not apply to rigid or intermediate metal conduit with listed steel or malleable-iron fittings and boxes, or to decking covered by 2 in. of concrete.

What changed in 2023

The 2023 edition made the 1¼ in. setback apply from every edge of the wood member, not just the nearest edge, and in the bored-hole exception replaced the old rigid nonmetallic conduit wording with rigid PVC conduit and RTRC.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond