NEC 250.66 · Homes and commercial

Sizing the grounding electrode conductor

The grounding electrode conductor is sized from Table 250.66 by the largest hot conductor supplying the system. Runs only to ground rods never need more than 6 AWG copper; runs only to a concrete-encased electrode never need more than 4 AWG copper.

What the code requires

The grounding electrode conductor connects the electrical system to its grounding electrodes, such as rods, a water pipe or a concrete-encased electrode. Table 250.66 sizes it from the largest ungrounded (hot) supply conductor. For parallel sets, the combined area of the conductors is used.

Supply conductor size, then electrode conductor size (Cu = copper, Al = aluminum): 2 AWG Cu or 1/0 Al and smaller, 8 Cu or 6 Al; 1 or 1/0 Cu, or 2/0 or 3/0 Al, 6 Cu or 4 Al; 2/0 or 3/0 Cu, or 4/0 or 250 kcmil Al, 4 Cu or 2 Al; over 3/0 through 350 kcmil Cu, or over 250 through 500 kcmil Al, 2 Cu or 1/0 Al.

Larger services: over 350 through 600 kcmil Cu, or over 500 through 900 kcmil Al, 1/0 Cu or 3/0 Al; over 600 through 1100 kcmil Cu, or over 900 through 1750 kcmil Al, 2/0 Cu or 4/0 Al; above that, 3/0 Cu or 250 kcmil Al.

On the job

  • For a 200 A home service on 2/0 copper or 4/0 aluminum conductors (sized under 310.12), the conductor to the water pipe or Ufer is 4 AWG copper, while 6 AWG copper is enough for a run that goes only to ground rods.
  • An undersized grounding electrode conductor to the water pipe is a common correction.

Exceptions that matter

  • A section that runs only to rods, pipes or plates never needs to be larger than 6 AWG copper or 4 AWG aluminum or copper-clad aluminum.
  • A section that runs only to a concrete-encased electrode never needs to be larger than 4 AWG copper.
  • A section that runs only to a ground ring never needs to be larger than the ring conductor.

What changed in 2023

The 2023 edition applied the section to bonding jumpers that connect electrodes together and added copper-clad aluminum to the rod-only size limit; the table values did not change.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond