NEC 240.67 · Commercial

Arc energy reduction for fuses of 1,200 A and up

Where fuses rated 1,200 A or more are installed, the fuse must clear within 0.07 second at the available arcing current, or one of the energy-reducing methods the code lists must be provided, with documentation and on-site testing.

What the code requires

240.67 applies wherever fuses rated 1,200 A or higher are installed.

The fuse must clear in 0.07 second or less at the available arcing current. If it does not, one of these must be provided and set below the arcing current: differential relaying, energy-reducing maintenance switching with a local status indicator, an energy-reducing active arc-flash mitigation system, current-limiting electronically actuated fuses, or an approved equivalent means.

Documentation must show where the fuses are and that the chosen method is set below the available arcing current. It must be available to those authorized to design, install, operate or inspect the installation. The method must be performance tested when first installed on site, by qualified persons following the manufacturer's instructions, using primary current injection or another approved method. A written record of the test must be available to your inspector.

On the job

  • Large switchboard fuses installed with no arc-energy documentation or test record are a common holdup at final inspection.
  • The documentation must show the fuse locations and that the method is set below the available arcing current, and it must be available to your inspector.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond