NEC 230.24 · Homes and commercial

Overhead service wire clearances over roofs and yards

Overhead service wires must be at least 8 ft 6 in. above a roof, with exceptions. Above ground, minimums range from 10 ft at the drip loop to 18 ft over public streets and 24 ft 6 in. over railroad tracks.

What the code requires

Overhead service conductors, the overhead wires that bring power to a building, must not be readily accessible. 230.24 sets minimum clearances above roofs and above the ground for services of 1,000 V or less.

Above a roof, the wires must be at least 8 ft 6 in. above the roof surface, and that clearance must be kept for 3 ft in all directions from the roof edge. The code lists five exceptions to the roof clearance; all five are summarized below.

Above final grade: 10 ft at the service entrance, the drip loop and pedestrian-only areas (only for messenger-supported cable at 150 V or less to ground); 12 ft over residential property, driveways and commercial areas without truck traffic, at 300 V or less to ground; and 15 ft over those same areas above 300 V to ground.

18 ft is required over public streets, alleys, roads, truck parking areas, non-residential driveways and cultivated, grazing, forest or orchard land, and 24 ft 6 in. over railroad tracks. Clearance over swimming pools follows 680.9.

On the job

  • A service mast that is too short, so the drop runs closer than 8 ft 6 in. over a low-slope roof, is a common correction.
  • A drip loop lower than 10 ft above grade.
  • A service drop crossing a driveway lower than 12 ft.

Exceptions that matter

  • Where the roof area gets pedestrian or vehicle traffic, the clearance above it must instead meet the ground clearances in 230.24(B).
  • At 300 V or less between conductors on a roof sloped at least 4 in. per 12 in., the roof clearance may be reduced to 3 ft.
  • At 300 V or less between conductors, the clearance above only the roof overhang may be reduced to 18 in. where no more than 6 ft of conductors, 4 ft measured horizontally, pass over the overhang and they end at a through-the-roof raceway or approved support.
  • The 3-ft clearance beyond the roof edge does not apply to the final span where the service drop or overhead service conductors attach to the side of the building.
  • At 300 V or less between conductors, where the roof area is guarded or isolated, the roof clearance may be reduced to 3 ft.

Related sections

  • NEC 225.19
  • NEC 230.26
  • NEC 230.28
  • NEC 230.29
  • NEC 680.9

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond