NEC 220.53 · Homes

Demand factor for four or more fixed appliances

In a standard-method dwelling load calculation, four or more fastened-in-place appliances rated ¼ hp or 500 W or more may be counted at 75% of their nameplate total. Cooking equipment, dryers, space heating, air conditioning and EV chargers are left out.

What the code requires

When calculating the load on a home's feeder or service with the standard method, the NEC allows a 75% demand factor on the combined nameplate ratings of four or more fastened-in-place appliances on the same feeder or service. Each appliance must be rated ¼ hp or more, or 500 W or more. This applies to one-family, two-family and multifamily dwellings.

Some appliances can never be part of this group: fastened-in-place cooking equipment, clothes dryers, space-heating equipment, air-conditioning equipment and, since 2023, electric vehicle supply equipment (EVSE).

On the job

  • EV chargers are figured separately under 220.57, at 7,200 W (VA) or the nameplate rating, whichever is larger.
  • Example: qualifying appliances totaling 8,400 VA count as 6,300 VA after the 75% factor.
  • With fewer than four qualifying appliances, the factor does not apply and they are counted at full nameplate.
  • The optional calculation in 220.82 handles fastened-in-place appliances differently, adding their nameplate ratings to the general loads instead of applying this 75% factor.

What changed in 2023

The 2023 NEC added electric vehicle supply equipment to the list of equipment that cannot use the 75% factor.

In California

For new construction, the 2025 CEC (625.1.1) also requires electric vehicle charging to comply with CALGreen, the California Green Building Standards Code.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond