NEC 110.14(D) · Homes and commercial

Tightening terminals to the required torque

Where the equipment or the manufacturer's instructions give a tightening torque value, terminals must be tightened to that value, and an approved means, such as a torque tool, must be used to reach it.

What the code requires

When equipment has a tightening torque marked on it or given in its installation instructions, its terminal connections must be tightened to that value. Under the 2023 NEC, an approved means must be used to achieve it.

An informational note gives examples of approved means: torque tools, plus shear bolts and breakaway-style devices that have visual indicators. If the manufacturer gives no torque value, a second note points to Informative Annex I or to the manufacturer. A third note refers to NFPA 70B for torquing threaded connections.

Older checklists may say a calibrated torque tool is required. That was the 2017 wording. Since the 2020 edition, the rule has called for an approved means instead, and the 2023 edition keeps that approach.

On the job

  • Inspectors may ask how torque was achieved. A torque screwdriver or torque wrench is the usual approved means.
  • NEMA recommends against re-torquing terminations after the initial installation and points to infrared scans and visual checks for finding loose connections. If a torque check is absolutely necessary, NEMA calls for de-energizing the circuit and setting the tool to 90% of the value.
  • Because torque values come from the manufacturer, they are also enforceable through 110.3(B), which requires equipment to be installed per its listing instructions.

Related sections

Where this comes from

0/300

Answers come from this library only and are written by AI. They can be wrong, so check the cited section and confirm with your building department.

San Clemente · South OC to North County San Diego

Send a photo. Get a real answer.

Text is fastest, and a photo quote is free. Call if it is urgent, if you smell something burning, or if a breaker will not reset.

CSLB #354550 · C-10 Electrical · Licensed since 1978 · $25,000 contractor's bond