Kitchen remodel electrical: lighting, circuits and code

A remodeled kitchen in California usually needs 10 to 12 new circuits: two 20-amp countertop circuits, a lighting circuit, and one for each built-in appliance, including a 40- or 50-amp, 240-volt circuit for an induction or pro range. Since January 1, 2026, the 2025 California Electrical Code (the 2023 NEC) has required GFCI on every kitchen receptacle and on the range, ovens, cooktop, dishwasher and microwave, and Title 24 wants every light JA8-certified with a wall dimmer.

By Shane Farmer and CK Electric and Sons · CSLB #354550Updated 19 sources

The short version
  • Two 20-amp small-appliance circuits are the code minimum, and lights can’t share them.
  • Pick the appliance models before the rough-in. A 36-inch induction cooktop can want 40 A or 50 A depending on the brand.
  • Islands no longer need receptacles under the 2023 NEC, but they need provisions for one, and below-counter receptacles are out.
  • Title 24: JA8 light sources, airtight no-screw-base downlights, a wall dimmer, and under-cabinet lights on their own control.
  • Induction adds a 240-volt breaker taking two panel spaces (two breakers for a 48-inch). Run the load calculation before you buy.
  • Expect a permit with at least a rough and a final inspection, and working smoke and CO alarms before sign-off.
Modern kitchen with cove lighting above the cabinets, LED-lit glass-front cabinets, under-cabinet lighting and two polished nickel dome pendants over a taupe island

What circuits does a remodeled kitchen need?

The code’s floor is two 20-amp small-appliance circuits for the countertop, wall and floor receptacles (NEC 210.11(C)(1) and 210.52(B)). Those circuits can’t serve anything else, so the lights get their own. Every built-in appliance adds one more, sized by its install guide: a dishwasher on 15 or 20 A (Bosch), a refrigerator on 15 A (Sub-Zero), a 48-inch dual-fuel range on 50 A (Wolf).

Refrigerators are where code and the install guides part ways. Code lets a refrigerator share a small-appliance circuit or have its own 15-amp-or-larger circuit (210.52(B)(1), Exception 2). Built-in makers like Sub-Zero want a dedicated circuit for each unit, and with column refrigeration that’s one per column.

A typical induction kitchen with a dishwasher, disposal, microwave drawer, hood, refrigerator, island receptacles and new lighting comes to 10 circuits and 11 panel spaces. Swap in a 48-inch dual-fuel range, a refrigerator column and a freezer column, a beverage fridge and pop-up receptacles and it’s 12 circuits and 13 spaces. The kitchen circuit planner builds your list with the code reference for each line.

Typical remodeled-kitchen circuits under the 2025 California Electrical Code
CircuitBreakerGFCIAFCIWhy it’s there
Countertop small-appliance circuit (×2 minimum)20 A, 120 VRequiredRequiredRequired by code
Island small-appliance circuit20 A, 120 VRequiredRequiredRecommended practice
30-inch induction range (GE Profile)40 A, 240 VRequiredNoRequired by the install guide
30/36-inch pro induction range (Wolf)50 A, 240 VRequiredNoRequired by the install guide
48-inch dual-fuel range (Wolf)50 A, 240 VRequiredNoRequired by the install guide
36-inch induction cooktop50 A, 240 VRequiredNoRequired by the install guide
Double wall oven (Wolf)50 A, 240 VRequiredNoRequired by the install guide
Dishwasher20 A, 120 VRequiredRequiredRequired by the install guide
Disposal20 A, 120 VIf it plugs inRequiredRecommended practice
Microwave drawer15 A, 120 VRequiredRequiredRequired by the install guide
Refrigerator or each column unit15 A, 120 VRequiredRequiredRequired by the install guide
Range hood (plug-in)15 A, 120 VIf it plugs inRequiredRequired locally
Kitchen lighting15 A, 120 VNoRequiredRequired by code

How should a high-end kitchen be lit?

In four layers, each on its own control: recessed ambient light, under-cabinet task light, low accent light, and decorative pendants. Rely on one grid of ceiling cans and you’ll put your own shadow on the counter every time you stand at it.

Ambient. Golden Lighting’s layout guide sets recessed lights 24 to 30 inches out from the cabinet line and about 4 feet apart on an 8-foot ceiling. Run the lumen method on a 16-by-12-foot kitchen with an 8-foot ceiling and it comes out to 12 six-inch wafers at 950 lumens, a 3-by-4 grid with the lights 4 feet apart. The recessed lighting layout tool draws yours to scale.

Task. Under-cabinet strips belong toward the front edge of the upper cabinets so the light hits the work surface instead of the backsplash. Accent. Toe-kick and in-cabinet lights are the low glow you leave on at night. Lights inside cabinets and drawers get a break on JA8 if they make at least 45 lumens per watt, but lighted drawers and opaque cabinets have to switch off when they close.

Decorative. Golden Lighting hangs island pendants 30 to 36 inches above the counter on an 8-foot ceiling, about 3 inches higher for each extra foot of ceiling, and spaces them 24 to 30 inches apart center to center. The same guide suggests 2,700 to 3,000K for ambient light and 3,000 to 3,500K over work areas. For the ceiling work itself, see recessed and interior lighting.

Dimming and scenes: what’s required and what’s worth it?

A readily accessible wall dimmer is required for kitchen lighting under Title 24 §150.0(k)2F, and the under-cabinet lights have to be controlled separately from the ceiling lights. That’s already two controls. Wire each layer on its own switch leg and you get scenes for free: cans and under-cabinet at full for cooking, pendants and toe-kick low for evening.

The dimmer has to suit the fixture. The Energy Commission’s FAQ says a forward phase-cut dimmer controlling LEDs must comply with NEMA SSL 7A, and a mismatched dimmer is where the buzz and the low-end flicker come from. We match the dimmer to the LED driver when we trim out, and a scene keypad or smart dimmer can replace a gang of switches as long as each layer stays independently dimmable.

What does California’s Title 24 require for kitchen lighting?

Every light source you install has to be JA8-certified under the 2025 Energy Code (Compliance Manual p. 6-1). Lights built into range hoods don’t need it, and neither do in-cabinet lights of 45 lumens per watt or better.

Recessed downlights carry extra rules (§150.0(k)1C, pp. 6-3 and 6-4):

  • No screw-base socket, and a light source marked “JA8-2025-E” for the elevated-temperature test.
  • Under an insulated ceiling: labeled airtight, under 2.0 cfm at 75 pascals (ASTM E283), and sealed to the drywall with a gasket or caulk.
  • IC-rated if insulation will touch it; a non-IC housing needs insulation held 3 inches away.

In a remodel, new or altered lighting has to meet all of §150.0(k), while fixtures you don’t touch can stay. Existing screw-base cans may keep their sockets if they get JA8-compliant trim kits made for recessed downlights. The installer signs a CF2R-LTG certificate for the lighting (p. 6-10).

If the remodel takes in a laundry room or a walk-in closet, at least one light there needs an occupancy or vacancy sensor that shuts it off on its own (p. 6-8).

How do you get power to an island now?

Island and peninsula receptacles are optional under the 2023 NEC, but if you skip them the island still needs provisions for adding one later (210.52(C)(2)). The 2020 rule that counted square feet of island top is gone. The code doesn’t say what “provisions” means, a point NAHB raised against the change, so ask your inspector what they’ll accept before the slab or subfloor closes.

If you’d like receptacles there, 210.52(C)(3) gives two places for them: on or above the counter, no more than 20 inches up, or in the countertop using an assembly listed for countertop use. That second option is the pop-up. The old option of mounting receptacles on the cabinet side below the counter was removed, because cords hanging off an island edge are what kids pull on. Island receptacles are countertop receptacles, so they ride on a 20-amp small-appliance circuit with GFCI and AFCI. We’d give the island its own. A microwave drawer in the island needs a separate 15-amp circuit (Wolf).

Going induction: can your panel take it?

An induction range needs a 240-volt breaker of 40 or 50 amps, and it’ll take two panel spaces. GE rates its 30-inch Profile PHS930 at 12.5 kW on a 40 A circuit. Wolf asks for 50 A on its 30- and 36-inch induction ranges and two separate 50 A circuits for the 48-inch. Cooktops vary just as much: Samsung’s 36-inch induction cooktop is 8.9 kW on 40 A, while Wolf’s 36-inch wants 50 A. Wolf also says its induction ranges aren’t designed for 208 volts and lose performance below 240.

Coming from gas, that circuit is new load, and it usually arrives alongside other new circuits. The panel load calculator runs the NEC calculation for your house with the new range in it. If the numbers or the open spaces aren’t there, a panel or service upgrade goes on the schedule before the appliance delivery, not after.

Why is almost every kitchen breaker GFCI, AFCI or both?

Under the 2023 NEC every kitchen receptacle up to 250 volts needs GFCI (210.8(A)(6)), and 210.8(D) adds dishwashers, electric ranges, wall ovens, cooktops and microwave ovens whether they’re plugged in or hardwired. Every 120-volt, 15- or 20-amp kitchen circuit also needs AFCI (210.12(A)). A dishwasher or microwave circuit needs both, so it’s usually a dual-function breaker.

Not everyone’s happy about it. NAHB asked states to delete the cooking-appliance GFCI rule over nuisance tripping, and Sub-Zero’s install guide calls GFCI “not recommended” on its indoor refrigerators. We found no California amendment, and Aliso Viejo’s March 2026 kitchen handout lists GFCI for dishwashers, ranges, wall ovens, cooktops and microwaves as written. The inspector enforces the code.

Permits, inspections and working with your GC

You’ll need a permit. Aliso Viejo’s handout requires one when cabinets, countertops, the sink, the dishwasher, an island, the electrical or the exhaust hood are removed, replaced or moved. It calls for at least two inspections, rough (after the boxes are in) and final, and the smoke and carbon monoxide alarms get checked during any permitted remodel. Other South County cities publish their own lists; the permit checker covers them.

CK Electric and Sons does remodel rough-in and trim-out for general contractors. What makes that go smoothly doesn’t change from job to job: appliance spec sheets and the cabinet drawings in the electrician’s hands before rough-in, receptacle and pendant locations marked on the plan, and the island decision made before the floor closes. Everything gets photographed before drywall, so nobody has to guess later where the wire runs. There’s more on how we work at rewires and remodel electrical.

Questions

Common questions

How many circuits does a kitchen remodel need?

Usually 10 to 12. The code minimum is two 20-amp small-appliance circuits plus a lighting circuit; each built-in appliance adds one, and a 48-inch induction range adds two.

How high should pendants hang over a kitchen island?

Golden Lighting’s guide says 30 to 36 inches above the countertop on an 8-foot ceiling, about 3 inches higher for each extra foot of ceiling height, with pendants 24 to 30 inches apart center to center.

Does switching to induction mean a panel upgrade?

Not automatically. An induction range needs a 240-volt, 40- or 50-amp circuit and two panel spaces; whether the service can carry it is a load calculation, not a guess. Run the panel load calculator with the range’s kW rating before you buy.

Can I put an outlet on the side of my kitchen island?

Not below the countertop anymore. Under the 2023 NEC, island receptacles go on or above the counter, no more than 20 inches up, or in the countertop as a listed pop-up or countertop assembly.

Do I need a permit for kitchen electrical work?

Yes, for a remodel. Aliso Viejo, for example, requires a permit whenever the electrical, hood, dishwasher, sink, island, cabinets or countertops are replaced or moved, with at least a rough and a final inspection.

Sources

Where this comes from

  1. ICC — 2025 California Electrical Code, Title 24, Part 3Based on the 2023 NEC; effective January 1, 2026 (read Sep 22, 2026).
  2. California Building Standards Commission — 2025 Title 24 California Code Changes2025 Title 24 codes effective January 1, 2026 (read Sep 22, 2026).
  3. California Energy Commission — 2025 Single-Family Residential Compliance Manual, Chapter 6: Residential LightingJA8 for all luminaires and its exceptions, including range-hood lights and in-cabinet lights of 45 lm/W or more (pp. 6-1 to 6-2); recessed downlight rules (pp. 6-3 to 6-4); kitchen dimmers, separately controlled under-cabinet lights, lighted drawers that shut off (p. 6-8); alterations and the CF2R-LTG certificate (p. 6-10) (read Sep 22, 2026).
  4. California Energy Commission — 2025 Residential Dwelling Units Lighting FAQs§150.0(k)2F dimmers in habitable rooms; forward phase-cut dimmers on LEDs must meet NEMA SSL 7A (read Sep 22, 2026).
  5. City of Aliso Viejo — Residential Kitchen Remodel handout (03/10/2026)When a permit is required, GFCI/AFCI/tamper-resistant receptacles, appliance GFCI, island provisions, 20 in limit, dedicated circuit for corded hoods, two inspections minimum, smoke and CO alarms during a permitted remodel (read Sep 22, 2026).
  6. InterNACHI — Kitchen receptacle requirements, 2024 IRC and 2023 NECTwo 20 A small-appliance circuits; 24 in rule; island receptacles optional with future provisions; 20 in limit; below-counter outlets no longer permitted (read Sep 22, 2026).
  7. NEC 210.52(C)(2) and (3), 2020 vs 2023 text (Electrical License Renewal)2023 text for islands and peninsulas; listed countertop and work-surface receptacle assemblies (read Sep 22, 2026).
  8. NEC 210.8(D) text comparison (Electrical License Renewal)2023 GFCI appliance list: dishwashers, electric ranges, wall-mounted ovens, counter-mounted cooking units, microwave ovens and others (read Sep 22, 2026).
  9. NAHB — Suggested amendments to the 2023 NECThe builders' objections to the new cooking-appliance GFCI rule, the island "provisions" wording and kitchen AFCI (read Sep 22, 2026).
  10. WireRef — Kitchen GFCI requirements, NEC 2023 210.8(A)(6)All kitchen receptacles 125–250 V on GFCI; AFCI on kitchen branch circuits (read Sep 22, 2026).
  11. Mike Holt forum — small-appliance circuit exceptions (NEC 210.52(B) quoted)What the small-appliance circuits serve, and the refrigeration exception (read Sep 22, 2026).
  12. Sub-Zero, Wolf and Cove — Wolf Design Guide (rev. 7/2025)Circuit sizes for Wolf induction ranges and cooktops, dual fuel ranges, ovens and drawers (read Sep 22, 2026).
  13. Sub-Zero, Wolf and Cove — induction range electrical requirements50 A dedicated; two separate 50 A circuits for the 48-inch model; not designed for 208 V, performance may drop below 240 V (read Sep 22, 2026).
  14. Sub-Zero Designer Series refrigeration installation guide15 A dedicated circuit per unit; GFCI "not recommended" indoors (read Sep 22, 2026).
  15. GE Profile PHS930 30-inch induction range specifications12.5 kW at 240 V; 40 A breaker (read Sep 22, 2026).
  16. Samsung CC70F36S2D 36-inch induction cooktop specifications240 V, 40 A, 8.9 kW (read Sep 22, 2026).
  17. Bosch dishwasher installation instructionsDedicated 120 V circuit on a 15 or 20 A breaker (read Sep 22, 2026).
  18. Golden Lighting — Kitchen lighting layout guideRecessed 24–30 in from the cabinet line, about 4 ft apart on 8 ft ceilings; pendants 30–36 in above the counter on an 8 ft ceiling plus about 3 in per extra foot, 24–30 in apart center to center; under-cabinet lights toward the front edge; 2,700–3,000K ambient and 3,000–3,500K task (read Sep 22, 2026).
  19. Lithonia Lighting — Wafer LED downlight WF4/WF6/WF8 SWW5 spec sheet950 lm and 12 W for the 6-inch at 3000K, used in the recessed-light example (read Sep 22, 2026).